Technische Details
MONOBLOCKWÄRMEPUMPE Luft/Wasser 12 kW
|
Aktuelles Produkt
10058005
|
Power Supply
|
|
|
220-240V~50/60Hz
|
Heating1
|
Capacity
|
kW
|
☼
|
4.20-12.20
|
Input Power
|
kW
|
☼
|
0.86-2.88
|
Input Current
|
A
|
☼
|
3.82-12.77
|
Heating2
|
Capacity
|
kW
|
☼
|
3.85-11.20
|
Input Power
|
kW
|
☼
|
1.13-3.75
|
Input Current
|
A
|
☼
|
5.01-16.6
|
Cooling
|
Capacity
|
kW
|
❄
|
2.60-10.30
|
Input Power
|
kW
|
❄
|
0.91-3.65
|
Input Current
|
A
|
❄
|
4.03-16.19
|
SCOP (Water Temp. At 35°C)
|
|
|
4.55
|
SCOP (Water Temp. At 55°C)
|
|
|
3.41
|
ERP Level (35°C)
|
/
|
|
A+++
|
Rated Input Power
|
kW
|
|
3.83
|
Rated Input Current
|
A
|
|
17
|
CO2 Equivalent
|
/
|
|
1.21t
|
Maximum Allowable
|
MPa
|
|
4.4
|
IP Class
|
/
|
|
IPX4
|
Max. Outlet Water Temp.
|
°C
|
|
60
|
Operating Ambient
|
°C
|
|
-25 ~ 45
|
Water Piping Connections
|
mm
|
|
G1
|
Rated Water Flow
|
m3/h
|
|
1.75
|
Water Pressure Drop
|
kPa
|
|
27
|
Noise Level
|
db(A)
|
|
51
|
Net Dimensions (LxWxH)
|
mm
|
|
1100x445x850
|
Net Weight
|
kg
|
|
107
|
Rated Test Conditions:
Heating1: Ambient Temp 7°C/6°C (DB/WB) Water-In/Out Temp 30°C/35°C
Heating2: Ambient Temp 7°C/6°C (DB/WB) Water-In/Out Temp 47°C/55°C
Cooling: Ambient Temp 35°C/24°C (DB/WB) Water-In/Out Temp 12°C/7°C
|
Technische Details (Stand März 2023).
Vorbehaltlich Druck- und Satzfehler sowie Irrtümer. Technische Änderungen erfolgen ohne vorherige Ankündigung.
